-40%

Omron Automation Safety H7CX-A4-N H7CXA4N 100-240AC Multifunction Preset Counter

$ 67.58

Availability: 60 in stock
  • Type: Counter Module
  • Restocking Fee: No
  • Item must be returned within: 30 Days
  • Condition: New
  • Return shipping will be paid by: Buyer
  • All returns accepted: Returns Accepted
  • MPN: H7CX-A4-N
  • Brand: Omron
  • Model: H7CX-A4-N
  • Refund will be given as: Money Back

    Description

    Omron Automation Safety H7CX-A4-N H7CXA4N 100-240AC Multifunction Preset Counter
    Specification:
    Function
    1 Stage Preset Counter / Total Preset Counter
    Preset stages
    1stages
    Rated supply voltage
    100 to 240 VAC 50/60 Hz
    Operating voltage range
    85% to 110% of rated supply voltage
    Power consumption
    Approx. 9.4 VA
    External power supply
    12 VDC (+/- 10%) 100 mA
    Counter (Count range)
    -999~9999
    Counter (Max. counting speed)
    30 Hz/5 kHz (switching) (Minimum counting input signal width: 16.7 ms(ON/OFF ratio: 1:1)/0.1 ms(ON/OFF ratio: 1:1))
    Common setting for CP1 and CP2
    Counter (Input mode)
    Increment decrement or increment/decrement (UP/DOWN A (command input), UP/DOWN B (individual input) and UP/DOWN C(quadrature input))
    Counter (Output modes)
    N / F / C / R / K-1 / P / Q / A / K-2 / D / L
    Counter One-shot time)
    0.01 to 99.99 s variable
    Counter (Reset system)
    External, manual and automatic reset (internal according to C, R, P and Q mode operation)
    Input signal
    CP1 / CP2 / Reset / Total reset
    Input method
    No-voltage/Voltage input (selectable)
    No-voltage input (No-contact input)
    Short-circuit (ON) impedance: 1 kΩ
    Leakage current (0 Ω): 12 mA
    Residual voltage: 3 V max.
    Open circuit impedance: 100 kΩ
    Maximum voltage: 30 V
    No-voltage input (Contact input)
    Use a contact which can adequately switch 5 mA at 10 V.
    Voltage input
    Hight level: 4.5 to 30 VDC
    Low level: 0 to 2 VDC
    Input resistance: 4.7 kΩ
    Applicable two-wire sensor
    leakage current: 1.5 mA
    Switching capacity: 5 mA
    Residual voltage: 3 V
    Operating voltage: 10 VDC
    Minimum input signal width
    External reset: 1 ms/20 ms (selectable)
    Standby time
    290 ms
    Control output (Contact output)
    SPDT
    Switching capacity: 3 A at 250 VAC/30 VDC, resistive load (cos phi=1)
    Minimum applicable load: 10 mA at 5 VDC (failure level:P reference value)
    Display method
    7-segment negative transmissive LCD
    Digits
    4digits
    Character height
    Count value: 12 mm (Red, green or orange programmable)
    Zero suppression: Equipped
    Set value: 6 mm (Green)
    Prescaling function
    Provided (0.001 to 9.999)
    Decimal point adjustment
    Rightmost 3 digits
    Key protection
    Key protect Switch
    Teaching function
    Not provided
    Batch counting function
    Not provided
    Communications
    Not provided
    Memory backup
    EEP-ROM (Number of rewite: 100000 times min.Service life: Approx. 10 years min.)
    Surrounding air temperature
    Operating: -10 to +55 ℃
    Storage: -25 to +70 ℃
    Ambient humidity
    Operating: 25 to 85%
    Storage: 25 to 85%
    Insulation resistance
    100 MΩ min. (at 500 VDC)
    Between current-carrying terminals and exposed non-current-carrying metal parts / Between non-continuous contacts
    Dielectric withstand voltage
    Between current-carrying metal parts and non-current-carrying metal parts:2000 VAC 50/60 Hz for 1 min
    Between power terminals and control input terminals:2000 VAC 50/60 Hz for 1 min
    Between control output,power supply, and input circuit:2000 VAC 50/60 Hz for 1 min
    Between non-continuous contacts:1000 VAC 50/60 Hz for 1 min
    Impulse withstand voltage
    Between power terminals:3.0 kV
    Between current-carrying terminal and exposed non-current -carrying metal parts:4.5 kV
    Noise immunity
    Between power terminals:+/- 1.5k V
    Between input terminals:+/- 600 V
    Square-wave noise by noise simulator (Pulse width: 100 ns/1 us, 1-ns rise)
    Static immunity
    8 kV (malfunction), 15 kV (destruction)
    Vibration resistance (Destruction)
    10 to 55 Hz with 0.75 mm single amplitude for two hours each in three directions
    Vibration resistance (Malfunction)
    10 to 55 Hz with 0.35 mm single amplitude for ten minutes each in three directions
    Shock resistance (Destruction)
    300 m/s**2 three times each in six directions
    Shock resistance (Malfunction)
    100 m/s**2 three times each in six directions
    Mechanical life expectancy
    10,000,000 operations min.
    Electrical life expectancy
    100,000 operations min. (3 A at 250 VAC, resistive load)
    Degree of protection
    Case front: IEC IP66, UL508 Type 4X (indoors) (when using the Y92S-29 Waterproof Packing)
    Mounting method
    Flush mounting
    External connection method
    Screw terminals
    Case color
    Black (Munsell N1.5)
    Accessories
    Flush mounting adapter / Waterproof rubber packing / Shock Prevention Cover
    Weight
    Approx. 130 g
    Package Included:
    1 x  Omron Automation Safety H7CX-A4-N H7CXA4N 100-240AC Multifunction Preset Counter
    6 months warranty
    60 days money backs
    Life-time support